Item
|
Standard
Specification
|
| Applicable
motor |
Rated
output /voltage |
200V
class: 30 to 90kW
400V class: 30 to 315kW |
| Revolution |
500,
1000, 1500, 1800 min.-1 |
| Input
power supply |
Voltage
(*1) |
3-phase
200/400VAC or 220/440VAC (within +10%/-15%) |
| Frequency |
50/60Hz
(within +/-5%) |
|
Control
method
|
Sine
wave PWM control, vector control, full-digital control, speed control,
torque control, auto field reduction control |
|
Overload
capacity
|
150%/min. |
|
Braking
method
|
Free-run
stop/option; engine braking (with braking resistor used) |
| Speed
control |
Operation
command |
Analog
input 0 to +/-10V (12-bit AD conversion) |
| Reversible
operation |
Switched
according to command input polarity or contact point |
| Speed
control range |
1:500 |
| Speed
fluctuation rate |
Digital
setting: +/-0.01%, Analog setting: +/-0.1% |
| Acceleration
/deceleration |
Linear
acceleration-deceleration/S-acceleration-deceleration changeover,
0 to 6000 sec. (individually settable for acceleration and deceleration) |
| Speed
feedback |
Encoder
(A, B, Z, U, V, W) |
| Torque
control |
Torque
command input |
+/-10VDC/max.
current |
|
Function
settings
|
Input
key switches |
|
Protective
features
|
Current
limit, overcurrent, overvoltage, load-side short, load-side grounding,
undervoltage, electronic thermal overload, start-time arm overcurrent,
start-time load-side overcurrent, dynamic braking resistance overcurrent/overload,
fin heating, emergency stop, etc. |
*1: +/-10% in case of